Vibration analysis and fault diagnosis of the fan unit and support structure
To eliminate the severe vibration of the E-GB110 Fan, the vibrations of the fan unit and the support structure were analyzed through local monitoring and finite element analysis in the paper. It was found that the synchronous vibration between the fan unit and the support system is the main reason. The rebuilding scheme was suggested based on optimization of the models. The support structure of the fan was rebuilt and the fan was overhauled. The efficiency is improved after rebuilding.
Fan Vibration Support structure Finite element
Shaoping Zhou Jie Zhang Yongsheng Su
School of Mechanical and Power Engineering, East China University of Science and Technology, Shanghai 200237, China
国际会议
国际断裂力学2007年会(Fracture Mechanics and Applications 2007)
长沙
英文
239-242
2007-11-01(万方平台首次上网日期,不代表论文的发表时间)