会议专题

Prediction of Energy Efficiency and Thermal Environment of Residential BuildingsUtilizing PEFC-CGS Combined Floor Heating System

The systematic numerical simulation program is developed to calculate the total energy efficiency of housing polymer electrolyte fuel cell co-generation system (PEFC-CGS) which is combined with hot water floor heating (HWFH). This simulation program can also predict actual building physics of heat transfer such as mutual radiant heat among interior surfaces and thermal strage relating with piping pitch of hot water and so on. The indoor temperature can be controlled by PMV (Predicted Mean Vote) to take account of thermal sensing affected radiant heat. As the results, it is clarified that the primary energy consumption is reduced up to 12% in winter because of the utilization of exhaust heat from PEFC-CGS and decreasing of indoor temperature for space heating by floor heating utility.

Residential building Fuel cell Co-generation system Hot water floor heating Thermal environment Energy conservation

Nobuyasu Ayagaki Akihito Ozaki Hiroto Takaguchi Hiroshi Kuroki Toshiyuki Watanabe

Sanki Industry Co., Tokyo, Japan, Kyoto Prefectural University, Kyoto, Japan, Waseda University, Tokyo, Japan, Daiwa House Industry Co., Osaka, Japan, Kyushu University, Fukuoka, Japan,

国际会议

第10届建筑模拟国际会议

北京

英文

2007-09-03(万方平台首次上网日期,不代表论文的发表时间)