PERFORMANCE ASSESSMENT OF A ROOFTOP NATURAL VENTILATOR POWERED BY HYBRID WIND AND PHOTOVOLTAIC ENERGY

In order to respond the suggestions made in the previous works, such as (1) improving the design of the rooftop ventilator commonly used in Taiwan, (2) making the “push-pull airflow model in the ventilation duct effective for the bathroom ventilation, and (3) combining the energy demands of the ventilator with renewable energy to reduce energy consumption, this study develops a prototype of the rooftop turbine ventilator powered by hybrid wind and photovoltaic energy. A low-speed wind tunnel experiment is performed to investigate the prototypes ventilation performance. The experimental results indicate installing an inner fan at low outdoor wind speed (0m/s, 5m/s) increases the ventilation rate. The ventilation rate was not improved by installing an inner fan at a high outdoor wind speed. A rated rotation speed close to 1500 rpm is highly recommended when installing the inner fan. This study also introduces the general application modes of the proposed ventilator, and their electricity specifications.

Ventilator Renewable energy Ventilation

Chi-ming Lai Yi-pin Lin Che-ming Chiang Yi-chang Chiang

Graduate Institute of Rural Planning, National Chung-Hsing University, Taiwan China Department of Architecture, National Cheng-Kung University, Taiwan China