会议专题

Study on Viscosity of Jet Fuel by CCD Near Infrared Spectrum

The analysis of viscosity in 50 jet fuel samples was studied using CCD near infrared spectroscopy. The NIR data were pretreated by the second derivative, and the calibration models were built using the partial least square (PLS) in the region of the 700-1100nm wavelength. High coefficients of correlation were obtained between the CCD near infrared spectroscopy prediction and those obtained from traditional chemical method. The result shows that the precision obtained through common chemical methods is almost the same as the one through CCD near infrared spectroscopy. The standard error of calibration (SEC) were 1.456, the determination coefficient (R 2 ) were 0.8321. This technique is well suitable for rapid quantitative determination of the Viscosity of jet fuel, and is simple, cheap, and can present real time result.

Near infrared spectrum CCD Jet fuel Viscosity PLS

Wu Ligang Wang Xuanjun Liu Xiangxuan Yang Weijun

Xian Research Inst.of Hi-tec Hongqing Town,Xian 710025 China

国际会议

第八届国际电子测量与仪器学术会议(Proceedings of 2007 8th International Conference on Electronic Measurement & Instruments)

西安

英文

2007-08-16(万方平台首次上网日期,不代表论文的发表时间)