Fault Location for Radial Feeders Based on Branch-Fault Diagnosis Method
A new approach to fault location for radial feeders in distribution networks is proposed based on branch-fault diagnosis method for analog circuits. The presented technique consists of two stages: line fault sector identification and distance estimation. It performs line fault detection by measuring the measurable node voltages responses corresponding to a particular current excitations applied at accessible nodes of distribution lines. The criterion of line fault sector identification and the corresponding fault location process are proposed. Based on it, a fault location system is developed, which consists of signal current source inject subsystem, voltage detection subsystem and communication subsystem. It is applicable to either single-phase fault or multiple-phase fault location.
fault location radial feeder branch-fault diagnosis voltage detection distribution network
Peng Minfang Tan Yi Shen Mei-E
College of Electrical and Information Engineering,Hunan University,Changsha,410082,China Beijing Information Technology Institute,Beijing,100101,China
国际会议
西安
英文
2007-08-16(万方平台首次上网日期,不代表论文的发表时间)