Removal of bioaerosols in HVAC system using the electret filters

This study utilized electret filters in the small-scale building heating, ventilating air conditioning (HVAC) system to remove the bioaerosols. Various factors, including the total air change per hour (total ACH), the fresh air change per hour (fresh ACH), and the relative humidity (RH) were considered to evaluate their effects on the bioaerosols decay behavior in the HVAC system with using electret filter. Results showed that decay constants of the E-Coli bioaerosol in the small-scale HVAC system without and with using electret filter were 0.183 (1/hr) and 0.708 (1/hr) (total ACH of 1.0 (1/hr) and fresh ACH of 0.18 (1/hr) ). That indicated that when the electret was applied in the HVAC system, the bioaerosol decay constant increased obviously. The results also presented that the bioaerosol decay constant (with electret filter) increased with total ACH and fresh ACH. The results implied that the decay constant of bioaerosols decreased with RH increasing.

bioaerosol HVAC system air change per hour relative humidity

YANG Shinhao LEE Grace Whei-may HUANG Hsiao-lin LUO Chin-hsiang HUANG Yi-chin WU Chih-cheng

Department of Leisure and Recreation Management, Toko University, Chia Yi County 613, Taiwan, ROC Graduate Institute of Environmental Engineering, National Taiwan University, Taipei 106, Taiwan, ROC Department of Occupational Safety and Health, Chia Nan University of Pharmacy & Science, Tainan 717, Department of Environmental Engineering, Hung-Kuang University, 34,Chung-Chie Rd., Sha-Lu, Taichung, Planning and Evaluation Division, National Science Council, Taiwan, ROC Chinasteel Corporation

国际会议

第4届居地建筑能源与环境国际研讨会

哈尔滨

英文

241-244

2007-01-15(万方平台首次上网日期,不代表论文的发表时间)