会议专题

EXPERIMENTAL RESEARCH ON GROUND SOURCE HEAT PUMP SYSTEM

A ground source heat pump system (GSHPs) with under-ground vertical U-tube heat exchanger was performed in north-west suburb of Beijing. The underground vertical U-tube heat exchanger of the water temperature versus the time change was tested for cooling and heating. The results showed that the water temperature of underground vertical U-tube heat exchanger of the ground-source heat pump system is relatively stable, average heating coefficient COP is 3.1 with out-let temperature of U-tube heat exchanger is 5.5~8.8 in ℃ winter, and average cooling coefficient COP is 4.6 with out-let temperature of U-tube heat exchanger is 22~26 in ℃ summer, respectively, so the GSHPs is highly efficient and energy-saving for heating and cooling.

He Duanlian Liu Qiming Yang Lin

Tsinghua solar facility Ltd, Beijing 100085, China

国际会议

2007世界太阳能大会(Proceedings of ISES Solar World Congress 2007)

北京

英文

2007-09-18(万方平台首次上网日期,不代表论文的发表时间)