RESEARCH OF CASCADE CONTROL WITH AN APPLICATION TO CENTRAL AIR-CONDITIONING SYSTEM

The heat exchanger and air-conditioning space in the central air-conditioning system are modeled in mathematic.Based on the models, we propose a cascade control strategy for temperature control of air-conditioning system.The setpoint response controller in the cascade control system is designed in terms of the robust control H2 optimal performance specification.According to the system operation requirement for disturbance rejection, a closed-loop for rejecting disturbance signals is configured and the controller in internal loop is figured out by proposing the desired closed-loop complementary function.Finally, the three controllers, the designed cascade control, traditional cascade P1D control and single PID control are simulated in central air-conditioning system.It is found that the setpoint response, the disturbance rejection, the robust and the performance of the designed cascade control system are better.

Cascade control Robust H2 optimal performance specification Air-conditioning system

JIANG-JIANG WANG CHUN-FA ZHANG YOU-YIN JING

School of Energy and Power Engineering, North China Electric Power University, Baoding 071003, China

国际会议

2007 International Conference on Machine Learning and Cybernetics(IEEE第六届机器学习与控制论国际会议)

香港

英文

498-503

2007-08-19(万方平台首次上网日期,不代表论文的发表时间)