FLOW BOILING OF REFRIGERANT R134a INSIDE A MICROFIN TUBE: EXPERIMENTAL TESTS AND PREDICTION
This paper reports the heat transfer coefficients measured during vaporisation of refrigerant R134a inside a microfin tube. This same tube was already tested during condensation of R134a. The experimental runs are carried out at 30 ℃ saturation temperature, with mass velocity ranging from 200 to 600 kg m-2 s-1 and heat flux from 42 to 86 kW m-2. The present data covers a vapour quality range between 0.08 and 0.93. The effects of vapour quality, mass velocity and heat flux on the heat transfer coefficient are investigated. The experimental data is compared to the condensation tests carried out on the same tube. This data is also compared to the prediction obtained by Cavallini et al. 1 model.
A.CAVALLINI D.DEL COL A.PADOVAN L.ROSSETTO
Dipartimento di Fisica Tecnica, University of Padova, Via Venezia 1 35313 Padova, Italy