CONTROLLING A 2-PHASE CO2 LOOP USING A 2-PHASE ACCUMULATOR
Mechanically pumped 2-phase fluid loops often have the problem of insufficient sub-cooling to operate the pumps without cavitation. This paper describes the use of 2-phase accumulators for controlling CO2 loops to obtain forced sub-cooling and accurate evaporator control. The technique of using 2-phase accumulators for loop control was first applied in satellite cooling.Two accumulator controlled loops have been successfully developed at NIKHEF. One CO2 loop for cooling the AMS particle detector which will study cosmic radiation onboard the International Space Station and a second CO2 loop is developed for cooling the LHCb-VELO particle detector which will study CP-violation at the CERN laboratory in Geneva (Switzerland).A 2-phase accumulator has the advantage of controlling the evaporator and condenser pressures independent of the primary cooler temperature. It is therefore possible to create as much sub-cooling for the pump as desired. It is even possible to operate the loop in single phase, a feature which turns out to be very convenient during start-up and cooling-down procedures. A 2-phase accumulator for evaporator pressure control in combination with an internal heat exchanger between the liquid feed and the 2-phase return line creates a very stable evaporator with a guaranteed evaporation at low vapor qualities. In this way the evaporator heat transfer can be tuned and evaporator dry-out is prevented.
Bart VERLAAT
National Institute for Nuclear Physics and High Energy Physics (NIKHEF) P.O. Box 41882, 1009 DB, Amsterdam, the Netherlands
国际会议
The 22nd International Congress of Refrigeration(第22届国际制冷大会)
北京
英文
2007-08-21(万方平台首次上网日期,不代表论文的发表时间)