会议专题

CONJUGATE NUMERICAL INVESTIGATE OF SMALL-SCALE FLAT PLATE CAPILLARY PUMPED LOOP EVAPORATOR

Two-dimensional numerical model for the small-scale flat plate capillary pumped loop (CPL) evaporator is presented, which includes liquid and vapor flow, heat transfer and phase change in the porous wick structure and heat transfer in the fluid region and metallic wall. The entire evaporator is solved with SIMPLE algorithm as a conjugate problem. The shape and location of vapor-liquid interface are calculated and the influences of applied heat flux, liquid subcooling and metallic wall material on the evaporator performance are studied. The effect of heat conduction of side metallic wall on the performance of small-scale flat plate CPL evaporator is analyzed, and sidewall effect heat transfer limit is introduced to estimate the performance of capillary evaporator. Increasing the liquid subcooling can increases the sidewall effect heat transfer limit of evaporator.

Zhongmin WAN W.LIU A.Nakayama

School of Energy and Power Engineering, Huazhong University of Science and Technology Wuhan, 430074, Department of Mechanical Engineering, Shizuoka University,3-5-1 Johoku, Hamamatsu, 432-8561, Japan

国际会议

The 22nd International Congress of Refrigeration(第22届国际制冷大会)

北京

英文

2007-08-21(万方平台首次上网日期,不代表论文的发表时间)