会议专题

CHARGING PERFORMANCE OF SEASONAL COLD STORAGE SYSTEM WITH SEPARATE TYPE HEAT PIPES

This paper presents a theoretical model for a specific seasonal cold storage system with separate heat pipes (SCSSHP).A quasi-steady state simulation model is established to analyze the charging performance of the system. The charging experiment has been carried out in Beijing to verify the theoretical model. The influences of various factors such as meteorological data, the length and radius of evaporating section and the fin coefficient of condenser section on the charging performance are analyzed with the model. It is shown that the atmosphere temperature is the most important factor affecting the charging capacity, the tube dimension of evaporator section should not be too long or too large, and the enhancement of heat transfer in condenser section is an effective way to increase the charging capacity of the cold storage system.

Chengchu YAN Wenxing SHI Xianting LI

Department of Building Science, Tsinghua University, Beijing, 100084, China

国际会议

The 22nd International Congress of Refrigeration(第22届国际制冷大会)

北京

英文

2007-08-21(万方平台首次上网日期,不代表论文的发表时间)