会议专题

EXPERIMENTAL STUDY ON DIRECT EVAPORATION ICE-ON-COIL THERMAL STORAGE SYSTEM

A direct evaporation ice-on-coil thermal storage experimental equipment was designed with the copper tube of diameter 16mm and wall thickness 1mm. The direct evaporation ice-on-coil can be arrayed at 100×100mm (system A), 100 × 50mm (system B) or 60 × 60mm (system C). The static states as well as dynamics direct evaporation ice-on-coil thermal storage experiment were done with disturbance and non-disturbance of refrigerated medium (water) in a ice tank. The experimental results show that with the increasing of the ice-on-coil array density, the thermal storage system performance improved markedly, and the performance of the disturbance system is better than the non-disturbance. According to the results of the direct evaporation ice-on-coil thermal storage experiment, compared with system A, system C shortens the time for 2-3 hours at the same storage capacity.

Yin LIU Guanghui ZHOU Angui LI

Zhongyuan Institute of Technology, No.41 Zhongyuan Road,Zhengzhou, 450007, P.R..China Xian University of Architecture and Technology, No.13 Yanta Road,Xian, 710055, P.R..China

国际会议

The 22nd International Congress of Refrigeration(第22届国际制冷大会)

北京

英文

2007-08-21(万方平台首次上网日期,不代表论文的发表时间)