会议专题

THE THEORETICAL STUDY OF THE HYBRID LIQUID DESICCANT EVAPORATIVE COOLING AIR-CONDITIONING REFRIGERATION CIRCULATION SYSTEM

This article presents a new hybrid evaporative cooling air-conditioning refrigeration system using two-stage liquid desiccant, and carries on the theoretical study on it. Compared with the conventional liquid desiccant air-conditioning refrigeration system, the new system adopts direct mixing heat transfer technology and evaporative cooling technology instead of water-cooled or air-cooled technology. Thus the cooling water usage is reduced. Using the two-stage adiabatic absorber and using refrigerant rather than water as the cooling medium of desiccant solution, the pressure difference of mass transfer is increased. Compared with the conventional system, the heat of regenerating solution is decreased because the mass ratio of air to desiccant solution is increased which gives rise to the decline of solution s mass rate. The results of theoretical calculation show that the new system has the better performance in power consumption, usage of water and equivalent coefficient of performance than the conventional system.

Liquid desiccant Evaporative cooling Two-stage absorber Equivalent coefficient of Performance

X.LIU W.Q.NIAN H.B.ZHANG

Xi an University of Architecture & Technology, School of Environmental &Municipal Engineering,Xi an 710055, Shanxi, China

国际会议

The 22nd International Congress of Refrigeration(第22届国际制冷大会)

北京

英文

2007-08-21(万方平台首次上网日期,不代表论文的发表时间)