PERFORMANCE OF A METAL HYDRIDE COOLING MODULE

Metal hydride technology is extended to cooling applications with two coupled reactors filled with two different metal hydrides. Such a cooling module filled with two different metal hydrides LaNi4.7Al0.3 and MmNi4.15Fe0.85 is simulated based on heat and mass transfer aspects. Hydrogen is cycled from one reactor to another by supplying/removing heat to/from them. The effect of variation of heat source, heat rejection and refrigeration temperatures for various cycle times has been studied in the ranges of 160 to 200℃, 30 to 50℃, 10 to -10℃ and 200 to 4000 seconds respectively. Both COP as well as SCP is found to increase with increase in heat source temperature at low cycle time. The effect of heat rejection temperature is to decrease COP. The SCP is found to be more at a low heat rejection temperature. High COPs and SCPs are delivered by the cooling module at higher refrigeration temperatures.

M.Ajay M.P.Maiya S.Srinivasa Murthy

Refrigeration and Air Conditioning Laboratory,Department of Mechanical Engineering,Indian Institute of Technology Madras,Chennai – 600 036, India