EFFECT OF CLIMATIC CONDITIONS ON THE PERFORMANCE OF GROUND SOURCE HEAT PUMP SYSTEM

Heating and cooling in buildings consume about 30% of the primary energy used in China. The most widely applied systems in this aspect are boilers and air-conditionings. Heat pumps are the only monovalent action way to satisfy the requirements of heating and cooling in many applications, because they can use renewable energy in the building’s surroundings. In this paper, a comparative discussion is given to the effect of climatic on applying ground source heat pump system technology. Analysis of the results can lead to the following conclusions: If only extracting heat from the earth, in two months, the soil temperature near the GSHP would be reduced to lower than 20℃. If only injecting mheat for three months, the soil temperature would be over 37℃, which is no longer suitable for air-conditioning. To preserve the ground resource for sustainable utilization as heat source/sink, it should be balanced between the heat injected to the ground and that extracted from the ground. Some measures can be considered in the design for the case of heat unbalance.

climatic condition Ground Source Heat Pump heat unbalance.

Xiangyun LIU Min YANG Ying CHEN Baoxin SHI

Faculty of material and energy, Guangdong University of Technology,Guangzhou, 510006,China