THERMODYNAMIC ANALYSIS AND COMPARISON OF TWO-STAGE CHLORIDE HEAT TRANSFORMERS

A two-stage heat transformer is superior to a single-stage one because it has higher efficiency or temperature lift. This paper carries out a systematic study on two-stage chloride heat transformers. On the basis of chlorides selection, four kinds of commonly used cycles, the resorption cycle (3S/G), double-effect resorption cycle (3S/G), two internal heat recovery resorption cycles (3S/G and 4S/G) are analyzed and compared according to coefficient of performance, exergy efficiency, temperature lift and some operational parameters.Among these four cycles, the resorption one (3S/G) is proved to be the best for driven heat temperature no more than 100 ℃. The double-effect resorption cycle (3S/G) has the highest COP, but lowest temperature lift. The two internal heat recovery resorption cycles (3S/G and 4S/G) have similar operation principle, but the 3S/G one is found to be the best at the driven heat temperature of 120 ℃ for its system pressure is smaller.