Retrofitting a complex, safety-critical PA system for periodic testing

  This paper describes considerations and the implementation of retrofitting a fully-automated procedure, for testing a public address system, into a safety-critical environment (a nuclear power plant).There are over 4000 loudspeakers, about 200 amplifiers as well as various alarm-signal generators that need to be tested every day within a few minutes.Additionally, all command room microphones are checked using a semi-automated procedure.The procedures were designed and configured to not only reliably detect single defective components, but also to not produce any false alarms.

Gregor Schmidle Philipp Schwizer Winfried H(a)ns

NTi Audio AG, 9494 Schaan, Liechtenstein Kernkraftwerk Gundremmingen GmbH, 89355 Gundremmingen, Germany