会议专题

Drainage Recycling of Valve-Cooling-System in the ±660kV Jiaodong Converter Station

  In HVDC power transmission projects,the AC power is converted into DC power in converter station and vice versa,so the converter valves are the core devices for energy conversion.The outside valve cooling system is designed to cool the inner cooling system in the DC converter station.The outside valve cooling system”s spray water is heated and evaporated constantly in the normal operation,leading to the concentration ratio become higher,and the conductivity would increase in continuous mode.When the conductivity reached certain valve,the balance tank drain valve will automatically start a large number of drainage.At the same time,the self-cleaning filter,softening device,sand filter during the running process will backwashing of drainage.The statistics in drainage quantity is 50000 m3,thus it would cause serious waste of water resources and increase the daily operational expenses.Regarding ±660 kV JiaoDong converter station as an example,the statistical analysis of drainage emissions was carried out on outside valve cooling system,according to the outside valve cooling system running water quality requirements,the best scheme was chosen for further study,which could provide feasible technical scheme of drainage recycling for the converter station”s outside valve cooling system,at the same time,the goal of energy conservation and emissions reduction could be achieved.

converter station outside valve cooling system drainage recycling reverse osmosis system

LIU Guo-qiang DAI Hai-tao XU Li-guo WU Zhong-jie ZHANG Yan

State Grid Hebei North Energy Conservation Service Corporation,Beijing 100045 China

国内会议

2016年中国电机工程学会年会

南京

英文

1-5

2016-11-15(万方平台首次上网日期,不代表论文的发表时间)