会议专题

Suppression of Arc Ignition for a DC Current Fuse Using a Transient Current Switched Circuit

  Fuses are important to protect circuits from heat when overcurrent is caused in the circuit.The fuse generates an arc discharge immediately after fusion.The AC arc discharge usually stops when the source voltage becomes zero.For conventional fuses, the high voltage DC arc discharge continues for a long time and might cause an electrical accident.We propose a transient current switched circuit to suppress arc ignition for fuses as well as electrical contact devices.The AC glass-tube fuse type (Specification: 10A.6.5mmψ×30mm) was confirmed to show an arcless current interruption for DC300V/30A and DC50V/100A.

Current fuse Arc ignition Transient current switched circuit DC current Arcless fuse

Daisuke Hara Noboru Wakatsuki

Ishinomaki Senshu University,Faculty of Science and Engineering,Ishinomaki,Miyagi,985-8580 Japan

国内会议

第十三届国际机电装置会议(IS-EMD2013)

武汉

英文

59-62

2013-11-16(万方平台首次上网日期,不代表论文的发表时间)