会议专题

Research on Controlling Water Quality of the Mixed Water of Desalted Water and Running Water Transmitted in Existing Drinking Water Distribution Systems

  The dynamic pilot scale experiments and static immersion experiments were done to study the effect of chemical parameters on iron release and turbidity when the mixed water of running water and desalinated water transmitted and distributed in drinking water distribution systems.The parameters include the different mixing ratios of running water and desalinated water,pH,alkalinity,chloride and sulfate.It was found that when the mixing ratio of running water and desalinated water 3:1,the iron release rate and turbidity change rate is smaller,the water quality is better.When the pH value was about 8.2,the phenomenon of iron release and the turbidity was controlled effectively.The improvement of alkalinity could reduce the turbidity and concentration of total iron.The concentration of total iron increased with the concentration of chloride and sulfate increasing.So,to guarantee the safety distribution of the mixed water of running water and desalinated water in drinking water distribution systems,the water quality condition should meet that the best mixing ratio of running water and desalinated water was 3∶1,pH value was about 8.2,and alkalinity was higher than 110mg/L.

desalinated water water distribution network iron release turbidity water quality indexes

Tong Hui-yan Zhao Peng Zhang Hong-wei Huang Chun-kai Tian Yi-me Liu Yang Jia Li-hua

School of Environmental Science and Engineering,Tianjin University,Tianjin 300072,China

国内会议

2012水资源与城市化发展大会

天津

英文

159-159

2012-09-26(万方平台首次上网日期,不代表论文的发表时间)