会议专题

Long Transmission Line Distance Protection Based on Parameter Identification

In this paper, a novel time-domain algorithm for long transmission line distance protection is proposed. When a certain fault occurs, the current and voltage at the end of the protection zone can be calculated by using the measured current and voltage at the relay. By applying the new algorithm, which has three coefficients needed to be resolved by time-domain differential equation and fits long distance transmission line, to the current and voltage data at the end of the protection zone, we will obtain the fault distance. When the computed distance is less than the setting value, we consider the fault as an internal fault. Theoretical analysis and simulation prove that this method is not affected by the distributed capacitance or aperiodic component. Furthermore, the algorithm works very reliably without overreaching and its speed is really fast. As to a 300km long transmission line with a 300Ω transition resistance, this algorithm is verified to be valid and accurate.

Distance Protection Transition Resistance Distributed Parameter Compensation Algorithm

SuonanJiale ZengchaoWang BinWang XiaoningKang

Department of Electrical Engineering,Xi’an Jiaotong University,Xi’an,Shaanxi 710049

国内会议

中国高等学校电力系统及其自动化专业第二十七届学术年会

秦皇岛

英文

1-6

2011-10-15(万方平台首次上网日期,不代表论文的发表时间)