Dynamic Simulation of an Air-conditioning System Utilizing Permanent-Magnetic Synchronous Frequency-Convertible Centrifugal Chiller
Building a dynamic simulation model of the centrifugal chiller in consideration of control processes is highly important for evaluating all-year performance of the chiller.A dynamic simulation model of the air-conditioning system utilizing PSF centrifugal chillers is built to simulate the dynamic operating parameter and performance in response to system control strategies.A simulation is conducted for a typical building in Guangzhou from May to October.Results show that the annual COP of the PSF centrifugal chiller reaches 7.33,and annual COP of the cooling station reaches 5.53.
simulation centrifugal COP control efficiency
Liu Hua Wang Sheng Liu Guolin
GREE Electric Appliances,INC.Zhuhai 519070,China